• ·        Features

     

     

    ·N+X parallel redundancy,support maximum 4 units in parallel

    ·Online double conversion with DSP control

    ·Optimization battery group,the quantity of battery: 16/18/20pcs    (32~40pcs supportable)

    ·Wide input voltage range: 208~478Vac

    ·Wide input frequency range: 40Hz~70Hz

    ·Input current harmonic: 3%

    ·Maximum charging current up to 18A (Settable)

    ·Support 3/1 and 1/1 operation

    ·Generator compatible

    ·ECO mode operation for energy saving

    ·Design with maintenance switch

    ·Cold start

    ·Intelligent fan speed regulation

    ·Self-testing when UPS startup

    ·50/60Hz frequency converter mode

    ·Multiple protection function: short-circuit, overload, overheat, battery overcharge and over discharge, output low voltage and     fan fault alarm

    ·Multiple communication interface: RS232/RS485/USB/EPO

    -Dry contact port (Relay card/SNMP card/Parallel cable/Battery     temperature sensor optional)

     

     

MODEL

Titanium PETA POWER PLUS 20 KVA ONLINE  3/1

Cabacity

20 KVA  / 20000 W

INPUT

 

Nominal voltage 

 380/400/415Vac (3PH+N+PE) 220/230/240Vac (L+N+PE)

Operating voltage range

208~478Vac; 120~276Vac

Frequency range

40~70Hz  (50/60Hz Auto-Sensing)   

Power factor

≥0.99

Bypass voltage range

Max.voltage:220V:+25% (Optional+10%,15%,20%)
230V:+20%
240V:+15%
Min.voltage:-45%

OUTPUT

 

Output voltage

220/230/240Vac (L+N+PE)

Power factor

1

Voltage regulation 

±1%

Output
frequency

±1%/±2%/±4%/±5%/±10% of the rated frequency
Bat. Mode :(50/60±0.1%)Hz

Crest factor

3:1

Harmonic distortion (THDv)

≤2% Linear load
≤5% Non linear load

Transfer time

0ms

Output waveform

Pure Sinewave

Overload 

AC Mode : Load≤110%: last 60min turn to bypass; ≤125%: last 10min  turn to bypass;≤150%: last 1min  turn to bypass; ≥150% turn to bypass mode immediately Bat.Mode : Load≤110%: last 10min; ≤125%: last 1min; ≤150%: last 5s; ≥150%: shut down UPS immediately
 Bypass Mode : Breaker 2X63A

EFFICENCY

 

EFFICENCY

94.5%

BATTERIES

 

Battery number

±96Vdc~±120Vdc (16~20pcs, 16pcs default, Standard unit and 20pcs no power derating; 18pcs output power factor 0.9; 16pcs output power factor 0.8)

Charging current (Max)

18A (Max.) 

Recharge time

Charging current can be set according to battery capacity

INDICATORS

 

LCD display

Input voltage,Input frequency,Output voltage,Output frequency,Load percentage, Battery voltage,Inner temperature& Remaining battery backup time

ALARM

 

Battery mode

Beeping every 4 seconds

Low Battery 

Beeping every second

Overload 

Beeping twice every second

Fault

Continously beeping

ENVIRONMENT

 

Operating temperature

0℃~40℃

Storage temperature

-25℃~55℃

Humidity range

20~95%RH @ 0~40℃ (Non condensing)

Altitude

<1500m,derating required when>1500m

Noise level

<58dB at 1 Meter

STANDARDS

 

Safety

IEC/EN62040-1,IEC/EN62477-1

EMC

IEC/EN62040-2,IEC61000-4-2,IEC61000-4-3,IEC61000-4-4,IEC61000-4-5,IEC61000-4-6,IEC61000-4-8

PHYSICAL

 

Dimension W x D×H (mm)

 250×580×655

Net weight (kg)

38

Specifcaions are Subject to change without prior notice 